DC Controller
UPC4 Master
User Manual
Page 15/100
©2010. ELTEK VALERE DEUTSCHLAND GmbH. UM_UPC4_V2.00_E_R1.1_2011-01-04
3.2.3 Power supply inputs/Relay outputs/MSTB Modbus connection
Figure 5. Power supply inputs/Relay outputs/MSTB Modbus connection
3.2.3.1 Power supply
Three power supply inputs are available (see Figure 5
.). The UPC4 must be supplied by 24 VDC ±10%
by external power supply units AC/DC or DC/DC. We recommend using not less than two (n + 1
redundancy) power supplies which are fed by save DC of the system.
Depending on the system (high voltage or low voltage) we
provide DC/DC converters as power supply
for the UPC4 Master as listed below:
Article code Designation
302-UP4-DCDC.LV Power supply, DIN rail mounting, Vi=18-75 VDC; Vo=24 VDC, Imax=2.5 A
302-UP4-DCDC.HV Power supply, DIN rail mounting, Vi=85-375 VDC; Vo=24 VDC, Imax=2.5 A
1 2
1 2
1 2
1 2 3 4
1 2 3
1 2 3
1 2 3
X8 (Modbus/Profibus)
X12 (Relay 1)
X13 (Relay 2)
X14 (Relay 3)
X2 (Power supply
input 1)
X4 (Power supply
input 3)
X3 (Power supply
input 2)