4.3 Battery backup systems
4.3.1 Temperature controlled output voltage
(Float charge of batteries in backup systems)
0°C 40°C T [°C]
U [V]
20°C
Figure 6. Diagram “Output voltage depending on temperature”
For this operation mode a temperature sensor of type KTY 81- 220 which is connected to a Basic-
Unit B
U is necessary.
The temperature information provided by the temperature sensor is analyzed by the UPC4 according
to the volt
age/temperature characteristic line. The output voltage for the CAN-Bus connected
rectifiers are controlled accordingly. This characteristic line linearly proceeds in an adjustable range
(e.g. 0°C…40°C) and is constant beyond this range (see illustration). The steepness of the characteristic
line is adjustable as the charge voltage difference, related to one battery cell and one degree C is
changed. The charge voltage difference of a lead acid battery is -2mV per cell and per °C by default.
(For details please see section 6.4.6 Battery
)