Installation Guide THEIA HE-t String Inverters 357115.033, Issue 2.0, 2011 March 15
There are three different configurations of the string box options:
1. Stringbox with DC fuse holders and DC switch
2. Stringbox with DC fuse holders and no DC switch
3. Stringbox with DC switch and no DC fuse holders
1. Stringbox with DC Fuse Holders and DC Switch
The stringbox can be equipped with DC fuse holders, DC switch and plug-in connectors or
cable glands.
Figure 2.3.6: Optional DC connectors
P1, P2, P3: Positive connectors
N1, N2, N3: Negative connectors
Figure 2.3.7: Stringbox with DC fuse holders and
DC switch
*N4: Grounding terminal and terminal for
the grounding strap
*P4: Ungrounded terminal
TB: Terminal Block
TBS: Terminal Block Screw
DS: DC Switch
Negative grounded PV String
Connect the grounding strap between *N4 and the DC ground terminal in the internal
connection area (See 2.3.2. Grounding).
Positive grounded PV String
Connect the positive conductors from the positive connectors to the terminal block labeled
Grounded and the negative conductors to the terminal block labeled Ungrounded.
Switch the conductors connected to *N4 and *P4.
Connect the grounding strap between *N4 and the DC ground terminal in the internal
connection area (See 2.3.2. Grounding).