16 Installation Guide THEIA HE-t String Inverters 357115.033, Issue 2.0, 2011 March
2. Stringbox with DC Fuse Holders and no DC Switch
The stringbox can be equipped with DC fuse holders and plug-in connectors or cable glands
and a blanking plug instead of the DC switch. A DC switch must be installed separately by
authorized personnel in compliance with the relevant national electrical regulations.
Figure 2.3.8: Optional DC connectors and no DC
switch
P1, P2, P3: Positive connectors
N1, N2, N3: Negative connectors
BP: Blanking Plug
Figure 2.3.9: Stringbox with DC fuse holders and
blanking plug
*N4: Grounding terminal and terminal for
the grounding strap
*P4: Ungrounded terminal
Negative grounded PV String
Connect the grounding strap between *N4 and the DC ground terminal in the internal
connection area (See 2.3.2. Grounding).
Positive grounded PV String
Connect the positive conductors from the positive connectors to the terminal block labeled
Grounded, and the negative conductors to the terminal block labeled Ungrounded.
Switch the conductors connected to *N4 and *P4.
Connect the grounding strap between *N4 and the DC ground terminal in the internal
connection area (See 2.3.2. Grounding).