Installation Guide THEIA HE-t String Inverters 357115.033, Issue 2.0, 2011 March 17
3. Stringbox with DC Switch and no DC Fuse Holders
This option is a stringbox equipped with DC switch and plug-in connectors or cable glands,
but there are no DC fuse holders.
Figure 2.3.10: Optional DC connectors and DC
switch
P1, P2, P3: Positive connectors
N1, N2, N3: Negative connectors
Figure 2.3.11: Stringbox with DC switch and no
DC fuse holders
**P1, **P2, **P3:
Terminals labeled Ungrounded
**N1, **N2, **N3:
Terminals labeled Grounded
**N4: Grounding terminal
**P4: Ungrounded terminal
**N5: Terminal for the grounding strap
DS: DC Switch
Negative grounded PV String
Connect the grounding strap between **N5 and the DC ground terminal in the internal
connection area (See 2.3.2. Grounding).
Positive grounded PV String
Connect the positive conductors from the positive connectors to the terminals **N1, **N2
and **N3, and the negative conductors to the terminals **P1, **P2 and **P3.
Switch the conductors connected to **N4 and **P4.
Connect the grounding strap between **N5 and the DC ground terminal in the internal
connection area (See 2.3.2. Grounding).