18 Installation Guide THEIA HE-t String Inverters 357115.033, Issue 2.0, 2011 March
2.3.3.2. No Stringbox: Connector Panel
The connector panel is equipped with plug-in connectors or cable glands. A DC switch must
be installed separately by authorized personnel in compliance with the relevant national
electrical regulations.
Figure 2.3.12: Connector panel with optional DC
connectors
N1, N2, N3: Negative connectors
P1, P2, P3: Positive connectors
Figure 2.3.13: Customer connection area
P1’, P2’, P3’:
Terminals labeled +POS (Positive)
N1’, N2’, N3’:
Terminals labeled –NEG (Negative)
G1: DC ground terminal (See 2.3.2.
Grounding)
Negative grounded PV String
• Connect the grounding strap between N3’ and G1.
• With three strings, two of the string conductors must be connected to the same terminal, so
that the grounding strap has a terminal for itself.
Positive grounded PV String
• Connect the grounding strap between P3’ and G1.
• With three strings, two of the string conductors must be connected to the same terminal, so
that the grounding strap has a terminal for itself.